EATON Digital Display Unit, LCD Display, 5 in L x 3-3/4 in W x 3-3/4 in H Dimensions
- Continuous reading of actual ground fault current, employing auto ranging
- Display of the pre-trip ground fault current, after a trip has occurred (flashing display)
- Display of the trip current setting, after a test trip has been activated
- Test and RESET pushbuttons
- The RESET button must be held pressed before the test is pressed to invoke the test procedure
- The function of this button can be enabled/disabled by inserting the interconnecting cable from the D64RPB100 relay into one of two sockets, TEST on or TEST off, on the right side of the display
- Pushing verify pushbutton shows if D64RPB100 tripped due to a ground fault prior to loss of its control voltage red trip LED lights or if there was no ground fault green run LED light strip-green run LED lights
- This indication will remain available for at least ten hours
- The numerical LCD window displays actual ground fault current in amps
- When a 5000:5 ratio interposing CT is used, all displayed values are to be interpreted as kA rather than amps
- Used with 30 ft of standard 4-wire telephone type cable connection
- Use with D64RPB100 Series B1 digital ground fault relay
-